What size fire pump do I need for my pool?
20 US gal/min at about 115.4 ft of total head is the required operating point in our worked example, not a rating for a kit. Your own outlet demand and measured layout set the requirement; use the maker curve to check it, and leave when officials direct you to evacuate.
Why is horsepower not enough?
A horsepower figure does not describe the required operating point. Use the maker performance curve and the complete layout to check that the pump can supply the outlets at the required head.
Can I combine maximum flow and maximum pressure?
Those headline values normally describe different operating conditions. Honda explains that flow must be read against total head and that friction losses reduce real performance. A hose or nozzle change can change the result.
How long will my pool last?
Divide usable gallons by the combined actual flow in gallons per minute. Our table is a constant-flow calculation; it excludes fuel limits, priming failures and changes in flow. It is not an operating-time promise.
Worked example
Assume two outlets each need 10 US gal/min at 40 psi. Combined demand is 2 × 10 = 20 US gal/min. Using Honda’s approximate 0.433 psi per foot of water, pressure head is 40 ÷ 0.433 = 92.4 ft. Add an assumed 5 ft suction lift, 8 ft rise and 10 ft friction loss at that flow: 92.4 + 5 + 8 + 10 = 115.4 ft total head. A maker curve must show at least 20 US gal/min at this head. These inputs are hypothetical; actual loss calculations and model-specific pump flow must be confirmed for your layout and pump model. No kit performance is asserted.
Our take
We would ask for a layout and an operating-point check before choosing between kits. Leave when officials direct you to leave, regardless of how much water remains.
Wildfire Defense Kit
Wildfire Defense Kit is $2,295 delivered, before sales tax. Supplemental equipment only. Installation is not included.
FAQ
Does a bigger pool need a bigger pump?
Pool size alone does not determine pump size. Required flow and total head do.
Does the runtime table size a pump?
No. It only divides assumed usable volume by assumed actual flow.
Can you certify my property from this article?
No. A property-specific review and the relevant authority remain separate.
Sources
The worked example above shows the original calculations and inputs (calculated 2026-11-08). These calculations are not field tests.
- powerequipment.honda.com (read 2026-11-08).
- www.readyforwildfire.org (read 2026-11-08).
By the Redgate Ranch & Home team. Published 2026-11-09. Sources checked 2026-11-08.
Read next: Can I use my swimming pool water for wildfire preparedness?.